Watts to Amps Calculator
Convert watts to amps (amperage) for DC, AC single-phase and three-phase circuits. Pick a voltage, enter the wattage, and get the current, apparent power and the breaker size to look at — instantly.
Leave at 1.0 for heaters, kettles and lights; use ~0.8–0.9 for motors, pumps, AC units and mixed loads.
Three-phase uses line-to-line voltage. Motor start-up surges draw several times these figures briefly. The breaker figure is a starting point for continuous loads (3 h or more) — wire size, local code and the appliance label decide the final rating.
Quick answer
Amps = Watts ÷ Volts for DC and resistive AC loads. For AC motors and mixed loads divide by Volts × power factor; for three-phase divide by √3 × Volts × power factor.
- 400 W at 12 V DC = 33.3 A
- 1,000 W at 120 V = 8.33 A · at 230 V = 4.35 A · at 240 V = 4.17 A
- 1,500 W heater at 120 V = 12.5 A (needs a 20 A circuit as a continuous load)
- 10 kW three-phase at 400 V, PF 0.9 = 16.0 A per phase
Going the other way? Use the amps to watts calculator.
How this conversion works
Amps = Watts ÷ Volts.For AC single-phase:
Amps = Watts ÷ (Volts × PF).For AC three-phase:
Amps = Watts ÷ (√3 × Volts × PF).Reverse the formula to go from amps back to watts. Apparent power (kVA) = real power (kW) ÷ power factor.
How to convert watts to amps
Power (watts) and current (amps) are linked by voltage. For a DC circuit, or an AC load that is purely resistive like a kettle or heater, current is simply power divided by voltage. AC loads with motors or electronics also have a power factor, which is the share of the supplied power that does useful work. These loads draw more current than their wattage alone suggests. Three-phase supplies spread the load across three conductors, which is where the √3 (≈ 1.732) comes in.
| Circuit | Formula |
|---|---|
| DC | A = W ÷ V |
| AC single-phase | A = W ÷ (V × PF) |
| AC three-phase (line-to-line V) | A = W ÷ (√3 × V × PF) |
| AC three-phase (line-to-neutral V) | A = W ÷ (3 × V × PF) |
Worked examples
Solar battery inverter: a 2,000 W load on a 12 V inverter pulls 2,000 ÷ 12 ≈ 167 A from the battery — before inverter losses of about 10%, so plan for roughly 185 A. The same load on a 48 V system draws about 46 A, which is why bigger systems move to 24 V or 48 V and why 12 V needs very thick cable.
Household circuit: a 1,800 W space heater on 120 V draws 15 A. Heaters run for hours, so they count as continuous loads: 15 × 1.25 = 18.75 A, which needs a 20 A circuit, not a 15 A one.
Motor load: a 1,000 W pump at 230 V with a power factor of 0.85 draws 1,000 ÷ (230 × 0.85) ≈ 5.1 A while running — and several times that for a moment at start-up, which matters for inverter and generator sizing.
Watts to amps chart — DC (12 V, 24 V, 48 V)
Current drawn from a battery or DC bus. Add about 10% if the load runs through an inverter.
| Watts | 12 V DC | 24 V DC | 48 V DC |
|---|---|---|---|
| 50 W | 4.17 A | 2.08 A | 1.04 A |
| 100 W | 8.33 A | 4.17 A | 2.08 A |
| 150 W | 12.5 A | 6.25 A | 3.12 A |
| 200 W | 16.7 A | 8.33 A | 4.17 A |
| 300 W | 25.0 A | 12.5 A | 6.25 A |
| 400 W | 33.3 A | 16.7 A | 8.33 A |
| 500 W | 41.7 A | 20.8 A | 10.4 A |
| 600 W | 50.0 A | 25.0 A | 12.5 A |
| 800 W | 66.7 A | 33.3 A | 16.7 A |
| 1,000 W | 83.3 A | 41.7 A | 20.8 A |
| 1,500 W | 125.0 A | 62.5 A | 31.2 A |
| 2,000 W | 166.7 A | 83.3 A | 41.7 A |
| 3,000 W | 250.0 A | 125.0 A | 62.5 A |
Watts to amps chart — AC single-phase (120 V, 208 V, 230 V, 240 V)
Power factor 1.0 (resistive loads such as heaters, kettles and incandescent lights). For motors, divide these figures by the power factor — e.g. by 0.85.
| Watts | 120 V | 208 V | 230 V | 240 V |
|---|---|---|---|---|
| 100 W | 0.83 A | 0.48 A | 0.43 A | 0.42 A |
| 500 W | 4.17 A | 2.40 A | 2.17 A | 2.08 A |
| 1,000 W | 8.33 A | 4.81 A | 4.35 A | 4.17 A |
| 1,200 W | 10.0 A | 5.77 A | 5.22 A | 5.00 A |
| 1,500 W | 12.5 A | 7.21 A | 6.52 A | 6.25 A |
| 1,800 W | 15.0 A | 8.65 A | 7.83 A | 7.50 A |
| 2,000 W | 16.7 A | 9.62 A | 8.70 A | 8.33 A |
| 2,400 W | 20.0 A | 11.5 A | 10.4 A | 10.0 A |
| 3,000 W | 25.0 A | 14.4 A | 13.0 A | 12.5 A |
| 3,600 W | 30.0 A | 17.3 A | 15.7 A | 15.0 A |
| 5,000 W | 41.7 A | 24.0 A | 21.7 A | 20.8 A |
| 7,200 W | 60.0 A | 34.6 A | 31.3 A | 30.0 A |
| 10,000 W | 83.3 A | 48.1 A | 43.5 A | 41.7 A |
Watts to amps chart — three-phase
Line current per phase at power factor 0.9, line-to-line voltage.
| Power | 208 V 3φ | 400 V 3φ | 415 V 3φ | 480 V 3φ |
|---|---|---|---|---|
| 5 kW | 15.4 A | 8.02 A | 7.73 A | 6.68 A |
| 10 kW | 30.8 A | 16.0 A | 15.5 A | 13.4 A |
| 15 kW | 46.3 A | 24.1 A | 23.2 A | 20.0 A |
| 20 kW | 61.7 A | 32.1 A | 30.9 A | 26.7 A |
| 30 kW | 92.5 A | 48.1 A | 46.4 A | 40.1 A |
| 50 kW | 154.2 A | 80.2 A | 77.3 A | 66.8 A |
| 75 kW | 231.3 A | 120.3 A | 115.9 A | 100.2 A |
| 100 kW | 308.4 A | 160.4 A | 154.6 A | 133.6 A |
Why the breaker is bigger than the current
Wiring codes treat anything that runs for three hours or more as a continuous load and require the overcurrent device to be rated at no less than 125% of that current. The calculator shows the 125% figure and the next standard rating: from the NEC list for US voltages (120, 208, 240, 277, 480 V) and from the common IEC miniature-circuit-breaker ratings elsewhere. The wire must be sized for the breaker, not just the load — check it with the wire size and voltage drop calculators.
New to the difference between the two kinds of supply? Read AC vs DC power explained.
Frequently asked questions
Divide the watts by the voltage: amperage = watts ÷ volts for DC and resistive AC loads. For AC motors and electronics also divide by the power factor, and for three-phase divide by √3 as well. 1,200 W at 120 V draws 10 A.
Divide watts by volts for DC or resistive loads. For AC, divide by volts times the power factor (single-phase), or by the square root of 3 times volts times power factor for three-phase.
400 W divided by 12 V is 33.3 A. If the 400 W is an AC load running through an inverter, the battery supplies about 37 A once roughly 10% inverter loss is included.
It depends on the voltage: 83.3 A at 12 V DC, 8.33 A at 120 V, 4.35 A at 230 V and 4.17 A at 240 V, for a resistive load.
12.5 A at 120 V and about 6.5 A at 230 V. Because heaters are continuous loads, a 1,500 W heater on 120 V should be on a 20 A circuit.
Use 1.0 for purely resistive loads such as heaters and incandescent bulbs, and roughly 0.8 to 0.9 for motors, pumps, air conditioners and mixed household loads.
Because amps equal watts divided by volts. At a lower voltage you need far more current to move the same power, which is why 12V systems require much heavier wiring than 230V ones.
This is the steady running current. Motor-driven loads briefly draw a start-up surge several times higher, which you must allow for when sizing inverters, generators and breakers.
Multiply amps by volts (and by the power factor for AC, or by 1.732 × volts × power factor for three-phase). The amps to watts calculator does this with its own reference chart.
Electrical unit converters
- Amps to watts calculator
- Watts to kilowatts calculator
- kW to kVA calculator
- Ohm's law calculator
- Ah to Wh calculator
- Ah to kWh calculator
- Amp-hours to amps calculator
- kWh to mAh calculator
- Watts to watt-hours calculator
- Joules to watts calculator
- HP to kW calculator
- BTU to kW calculator
- kWh to MJ calculator
- AWG to mm² calculator
Learn more
Sources & standards
These watts/amps/volts conversions follow standard SI unit definitions and the electrical-code power-factor conventions referenced below.
- The International System of Units (SI) — National Institute of Standards and Technology
Defines the watt, ampere and volt this calculator converts between. - NFPA 70 — National Electrical Code (NEC) — National Fire Protection Association
Source of the single-phase and three-phase current formulas, and the practice of sizing wiring and breakers to amps rather than watts. - NEMA MG 1 — Motors and Generators — National Electrical Manufacturers Association
Reference for the 0.8–0.9 power-factor range this calculator suggests for motor and pump loads.